BSV Series plate type NAMUR solenoid
valve is available in both 3/2 way (Single Acting) and
5/2 way (Double Acting) versions with IP65 enclosure.
The integral slot throttle structure design and high
precision finishing technique for valve hole allow for
positive shifting of air flow and constant clearing of
the spool with each shift, enabling the valve to stroke
millions of trouble-free cycles. The BSV series solenoid
valve is intended for use on all Valves with Quarter
Turn Preumatic Actuator that incorporate the standard of
NAMUR mounting paid (24mm x 32mm rectangle, 1/4:
connection).
The operating principle is as follows:
ENERGIZED
When the solenoid operator is
energized, the soleriod coil creates a magnetic field
surrounding the plunger assemblyplunger. The plunger is
lifted off its seat by this magnatic force and supply
air provides an internal pilotpressure that is directed
to the pillot piston that shifts the spool and
compresses the main spring. This shifting directs the
flow of supply air form inletport P tocylinder port A
while cylinder port B is connected to exhaust port R2.
DE-ENERGIZED
When the solenoid coil is
de-energized, a spring on the plunger will return the
plunger to its seat, blocking internal pilot air, and
the main spring will returns the spool to its normal
position. In this position, the spool directs flow of
supply air from inlet port P to cylinder port B while
cylinder port A is connected to exhaust port R1.
PARTS AND MATERIALS
NO
PART NAME
MATERIAL
QTY
01
NUT
PLASTIC
01
02
COIL
01
03
JUNCTION BOX
PLASTIC
01
04
PLUNGER
01
05
VALVE BODY
ALUMINIUM ALLOY
01
06
O-RING
NBR
02
07
SPOOL
ALUMINIUM ALLOY
01
08
FLAT RING
NBR
06
09
RHOMBUS RING
NBR
01
10
COVER
ALUMINIUM ALLOY
01
11
RETURN SPRING
SS
01
3/2 WAY DIRECT ACTING, NAMUR SOLENOID VALVE - BSV
231 (1/4" CONNECTION)